FAA L-824 Type C Shielded 5kV

FAA L-824 Type C Shielded 5kV    

Applications

These cables are used for interconnecting the transformers and the current regulator of airfield lighting systems in series circuits, suitable for fixed applications such as taxiways, runways, touchdown zones, land and hold short lighting systems, can be installed in conduit, duct, aerial and direct burial.

Standards

FAA AC 150 / 5345-7E
FAA L-824 Type C
ICEA S-93-639 / NEMA WC74

Construction

Conductor: Stranded bare or tinned copper.
Inner Semi-Conductor: Extruded semi-conducting compound.
Insulation: XLPE.
Outer Semi-Conductor: Semi conducting tape or extruded.
Shield: Copper or brass tape(s). Tinned copper wire braid can be offered upon request.
Sheath: PVC. PE/XLPE can be offered upon request.

Technical Data

Rated Voltage Uo/U (Um)

5kV

Maximum Conductor Temperature

90℃

Short Circuit Temperature

250℃

Operating Temperatures

-40℃~+90℃

Minimum Bending Radius

static: 10×OD; dynamic: 20×OD

Impacted Resistant Yes

Weather Resistant

Yes

Dimensions and Weight

Construction

No. of
Strand

Nominal Insulation
Thickness

Nominal Overall
Diameter

Nominal Weight

No.× AWG

-

mm

inches

mm

inches

kg/km

lbs/kft

1×6mm² 7/19 2.3 0.09 11.0 0.43 180 121

1×8

7/19

2.3

0.09

14.3

0.565

298

200

1×6

7/19

2.3

0.09

15.4

0.605

366

246

1×4

7/19

2.3

0.09

17.0

0.668

513

345